Envoy Installation and Operation
Copyright 2012 Enphase Energy 141-00011 Rev 03
36
3. Although optional, it is best practice to enter a value for Total Devices. Enter a value in
this field. The Envoy will stop scanning once it has detected the given number of
devices.
NOTE: The Total Devices option can be used in conjunction with the Priority Duration
option to help discover any last few microinverters at a large site.
4. Enter a Priority Duration (optional) in days:hours:minutes (e.g., 0:00:20 to indicate zero
days, zero hours, and 20 minutes). If you enter a value in this field, the Envoy will make
scanning its sole activity for the period specified.
NOTE: The Priority Duration option should only be used in limited situations, e.g., at
large sites or sites experiencing problems discovering devices with the normal scan.
5. Click Start Scan to complete this task. The LCD screen will display the following, where
“nnnn” represents the number of microinverters (devices) detected.
NOTE: No power production data will be collected or displayed on the Envoy or in
Enlighten while Priority Scan is active. Also, the Communication Check function will not
operate during this period.
Priority Scan is
Active Devs: nnnn